08/06 61
5.3 Frequency and percentage reference channel
he varied functions for the specification of the reference values are connected in the
various configurations by the frequency or percentage reference channel. The
Refer-
ence frequency source
475, and the Reference percentage source 476 determine the
additive connection of the available reference sources as a function of the installed
hardware.
Operation mode Function
2 -EM-S1INA, absolute value Reference source is the analog input EM-S1INA
4 -
MFI1A + EM-S1INA, abso-
lute value
Reference sources are the multifunctional input
MFI1A and the analog input EM-S1INA
14 -
MFI1A + EM-S1INA + FF,
absolute value
Reference sources are the multifunctional input
MFI1A, analog input EM-S1INA and fixed frequency
FF
24 -
MFI1A + EM-S1INA + MP,
absolute value
Reference sources are the multifunctional input
MFI1A, analog input EM-S1INA and the motor poten-
tiometer function MP
34 -
speed sensor 2 (F2), abso-
lute value
The frequency signals of the resolver are evaluated
using a fixed number of division marks of 1024 as a
reference value.
102 to 124 Operation modes with signs (+/-)
Additional to the operation modes listed, those stated in the operatin
instructions o
the frequency inverter in the chapter "Frequency reference channel“, and in the chap-
ter "Percentage reference channel“ also apply.
5.4 Actual value display
The actual value of speed sensor 2 can be read via the parameters Frequency
pee
sensor 2 219 and Speed, speed sensor 2 220.
The analog input signal on analog input EM-S1INA can be a volta
e or a current si
nal
depending on the setting of switch S3. Accordingly, the actual value parameter
Analo
input EM-S1INA 253 is displayed as a percentage.
5.5 Repetition frequency output EM-RFOUT
The repetition frequency output EM-RFOUT emulates a speed sensor. The repetition
frequency output delivers the frequency signal of the resolver as a simulation of an
incremental speed sensor with reference si
nal. The number of division marks is se
permanently to 1024 division marks, thus no parameterization is required.
For parameter
Repetition Freq. Operation 555 the additional operation mode 4 – Fre-
quency speed sensor 2 is selectable. It can put out the absolute value of
requency
speed sensor 2
219 to the multifunctional output MFO1 of the frequency inverter.
Assignment of the outputs:
Repetition frequency output EM-RFOUT (X410A.7): track A+
Repetition frequency output EM-RFOUT (X410B.1): track A-
Repetition frequency output EM-RFOUT (X410B.2): track B+
Repetition frequency output EM-RFOUT (X410B.3): track B-